Go Up

System Operation
Home
Profile
Training
Capabilities
Clients
PV Info
Links
Contact

This Level

Background
System 
 Operation
Mechanical 
 Room

The primary way of interacting with the system is through the four thermostats located across from the downstairs kitchen, in the north-facing living room near the kitchen, in the "workshop" next to the garage and in the master bedroom. Each thermostat is located near a zone (portion of the house) vent through which hot, cold or fresh air will come as requested by that thermostat. The output of the zone vent may not be as expected if one of two conditions occur: cooling can only occur if no thermostats are requesting heating, and if the "fan" switch is turned on for any of the thermostats then all zones will receive outside (vent) air.

The following figure is a ducting schematic that shows the ducting system and most of the active system components. Z-1 through Z-4 represent the four zones, including their dampers and thermostats. The "Heat Water" box represents the water heating coil and circulating pump. The arrows in the blowers indicate the direction of air flow. The arrow between dampers D-13 and D-12 represents the outdoor air inlet located in the crawlspace under the house. The arrow between D-11 and D-10 represents the outdoor air exhaust located near the top of the stairs at the back of the house. BDD1 is a backdraft damper that passively prevents air from flowing from the greenhouse into Rock Box 2 (in preference to air drawn from the return air inlets throughout the house).

ducting schematic that shows the ducting system and most of the active system components

The dampers include bidirectional 24VAC hysteresis motors with switches the close when the dampers are fully open or fully closed. The blowers use 120VAC motors. The heat pump is a 3-ton unit.  The rock boxes contain 35 tons of 3/4 inch rock, with space above and below the rock so the air flows equally through all the rock. The water heating system feeds a domestic hot water preheat tank to reduce electric consumption in the electric water heater.

Functions

The following discussion represents the results of the system analysis performed by Endecon Engineering, using design notes provided by Mike Kliment as a starting point. The original controller simplified these functional descriptions somewhat, which slowed system response and prevented certain low priority functions from working optimally.

The control computer must coordinate the operation of the system components to satisfy the needs of several different functions. The following functions are presented in order of decreasing priority. Lower     priority functions may not be able to activate (they are "blocked") if higher priority functions need to use the same components.

Zone Controller

In a small central space heating and cooling system of "conventional" design, a furnace would supply heat and an air conditioner would supply cooling to the central ducts. If we treated the house as a single    temperature zone, a thermostat would be connected directly to the furnace and air conditioner.  Expanding the system to include four different zones requires that a zone controller arbitrate between the (possibly) different requests from each of four thermostats. This arbitration process decides whether hot or cold air is delivered to the central ducts, and activates dampers to disable delivery of that air to zones that did not request it.

In this system, any request for heat overrides all requests for cooling (since it is not possible to both heat and cool at the same time, as there is only one central delivery duct).

Venting

This function uses blower 1 to vent the whole house (all zones) using outside air as the source. This function is activated by turning any of the thermostat "fan" switches on. This function has a very high priority, but is still subject to the constraints of the damper activation speed.

House Heating

House heating is performed by choosing the warmest available air and warming it if necessary using the heat pump.  If the hot rocks are hotter than 95°F then air is drawn from the house return air inlet through those rocks, through blower 2, and into the central delivery duct.  If the rocks are warmer than the outside air, then the heat pump draws heat from the rocks and puts it into the house return air using the condenser coils in blower 2.  If the rocks are cooler than the outside air but warmer than the return air, the heat pump will draw heat from the outside air to heat the evaporator and will draw the house return air through the rocks before heating it with the condenser coils.  If the rocks are not significantly warmer than the outside air, then the heat pump will simply draw heat from outside air.

One final mode is used if the heat pump is running, the boxes are split (summer mode), box 1 is warmer than the outside air, and box 2 is warmer than the house air.  In this (rare) case, the heat pump will draw heat from box 1 through the evaporator coils and draw return air through box 2 through the condenser coils.

House Cooling

House cooling is performed by choosing the coolest available air and cooling it if necessary using the heat pump. If the cool rocks are cooler than 65°F, then air is simply drawn from the house return air inlet     through those rocks, through blower 1, and into the central delivery duct. If the cool rocks are warmer than 65°F but still cooler than the return air, then the same air flow is used but the heat pump is turned on and blower 2 is used circulate outside air past the hot side of the heat pump. If the rocks are not cooler than the return air, then the house return air bypasses the rocks, entering blower 1 through damper 1.

Note that rock box 1 is only used for cooling if the "Summer" operating mode is turned on.

The 65°F rock temperature setpoint is a compromise between the typical target house temperature and likely available nighttime outdoor temperatures from which the cold box must be "recharged".  Setting it too low will reduce the effectiveness of the thermal mass in stabilizing the daily temperature swings, and setting it too high will raise the minimum temperature to which the system can cool the house.

Heat Collection

This function is always active, since the system cannot circulate hot air through the domestic hot water pre-heater without also passing that air through rock box 2. Since it only uses damper 1 and the circulating blower B3, and rock box 2 is always used for heating, there is no conflict between this function and any other functions.

Heat collection is activated whenever the collector temperature is significantly greater than the bottom-draw duct temperature from rock box 2.

Water Preheating

This function is always active, since it does not interfere with any other functions, and hot water is always needed. When the water heat exchanger coil is hotter than the preheat water tank, then the    circulating pump is turned on.

Greenhouse Venting

This function is always active. When the greenhouse temperature is greater than 85°F, the greenhouse vent is opened.

Cool Collection

When the summer mode is activated (the rock boxes are separated) and the outside temperature is significantly cooler than the top of box 1, this function will attempt to deliver cool air into rock box 1.

This function will be blocked if house cooling or any use of the heat pump is needed.

Send us your comments, or request that we contact you.

Endecon Enginering copyright, privacy policy and disclaimer statements.